Dear Editor,
We report a critical case of an electrical fire that erupted in the morning hours in the operating room (OR) of a tertiary hospital in Korea during a living-donor liver surgery. Before starting routine cases, heavy rainfall caused water leakage into the anesthesia equipment room, which houses electrical wiring and piped medical gases, resulting in a short circuit and subsequent ignition. Loud cracking sounds and electrical flashes, followed by visible flames near the anesthesia machine, rapidly escalated into an oxygen-enriched fire with intermittent explosions and dense smoke. The OR positive-pressure ventilation (PPV) system allowed rapid dissemination of smoke and toxic gases into adjacent ORs and corridors.
During the fire, a donor patient was under general anesthesia for laparoscopic lobectomy, after trocar insertion had already been performed. Seven staff members from the surgical team, anesthesia team, and OR nurses, were directly involved in the procedure. Although no other surgeries were in progress, the operating suite was being prepared for scheduled elective cases, with 40 staff members present within the operating complex. The surgical and anesthesia teams attempted to disconnect the patient from the anesthesia machine, but there was a delay of approximately three-minutes due to the unavailability of a portable oxygen cylinder. The anesthesia machine was then completely disconnected, and manual ventilation using an Ambu bag was initiated. During this interval, electrical power to the OR was shut off at the circuit breaker. However, oxygen delivery via the anesthesia machine was temporarily maintained despite the fire occurring adjacent to the workstation. Although the central oxygen pipeline remained intact, there were considerable concerns regarding possible fire propagation to the anesthesia machine or a sudden interruption of oxygen supply. Once an oxygen cylinder became available, the patient was fully disconnected from the anesthesia machine, and manual ventilation was continued using an Ambu bag with 100% oxygen.
Although the fire occurred in close proximity, the surgical team was compelled to cover and secure the surgical field to protect the patient’s open abdomen before evacuation. The evacuation was substantially impeded by the chaotic environment, such as dense smoke, toxic fumes, intense heat, intermittent sparks and explosions, which severely compromised visibility and significantly delayed the disentanglement of monitoring cables, intravenous lines, and patient restraints. An external transport stretcher was brought to the entrance of the OR, located near the main corridor. Following the fire detection, electrical power was immediately shut off, and the double-door system and high-efficiency particulate air-filtered doors were manually opened to expedite patient transfer. Due to the ongoing fire and evacuation constraints, a portable monitoring system was not immediately available in the OR. Given that the post-anesthesia care unit (PACU) was located approximately 10 meters away, the patient was promptly transferred with oxygen saturation as the sole monitoring parameter, and full monitoring was resumed only upon arrival in the PACU. After confirming hemodynamic stability, the patient was transferred to the intensive care unit (ICU). In the ICU, definitive abdominal closure was performed, and the patient awakened from anesthesia, uneventfully. During this period, anesthesia was maintained with intermittent administration of fentanyl and midazolam under emergent circumstances, with no complications.
The fire was ultimately extinguished by hospital firefighters using CO₂ extinguishers, as water-based sprinkler systems were ineffective for electrical fires in an oxygen-enriched environment. Several staff members were exposed to toxic smoke, while some required emergency medical treatment.
OR fires are rare but potentially catastrophic because all three components of the “fire triad”—an ignition source, an oxidizer, and a fuel source are inherently present in the OR [
1]. After the incident, a root-cause analysis identified multiple system vulnerabilities that compounded the risk and impeded an effective response.
Key system deficiencies include the absence of immediately accessible Class C (CO₂) fire extinguishers appropriate for electrical and oxygen-enriched fires, resulting in delayed and ineffective initial fire suppression, due to reliance on water-based extinguishers [
1–
3]. In this case, the presence of a piped oxygen source within the anesthesia pantry likely created an oxygen-enriched environment that sustained combustion, leading to rapid fire propagation and repeated small explosions, thereby making fire suppression particularly difficult [
1–
3].
In addition, ventilation systems lack rapid isolation or shutdown mechanisms, allowing smoke and toxic fumes to spread beyond the OR index [
2,
4]. Moreover, PPV systems cause rapid dissemination of smoke and toxic gases to adjacent ORs and nearby critical areas, presenting recognized hazards in positive-pressure procedural environments [
2]. When combined with insufficient emergency lighting, this severely impaired visibility and evacuation, posed an immediate risk of multidepartment involvement given the proximity to the ICU and emergency department, and resulted in smoke exposure among hospital staff, which required emergency medical evaluation. This incident emphasizes the absence of a dedicated institutional protocol [
2,
4].
Evacuating a patient under anesthesia in an open surgical field is challenging. Disentangling the airway equipment, monitoring cables, and infusion lines significantly delayed patient egress and prolonged the exposure of both patients and staff to smoke and heat. Despite coordinated efforts, evacuations take a considerable amount of time, consistent with previous reports, which indicate that OR evacuation during an active fire is particularly complex and time-critical [
5].
Despite fire safety education, the staff did not rehearse realistic OR fire scenarios involving a patient under anesthesia. Consequently, the initial response relied on individual efforts rather than a coordinated team approach, with momentary role confusion highlighting the gap between theoretical training and real-world emergencies [
2,
4]. Furthermore, the absence of a dedicated OR fire emergency protocol integrating surgical, anesthesia, and infrastructure control responses results in ad hoc decision-making and potential delays, highlighting that classroom instruction alone is insufficient without regular scenario-based drills [
2,
4].
Based on the root-cause analysis and existing fire safety guidelines, several key measures are recommended to mitigate OR fire risks. First, the OR safety infrastructure should be upgraded to ensure compliance with fire codes, including the immediate availability of an appropriate Class C (CO₂ or dry chemical) fire extinguishers, clearly marked emergency shut-off systems for oxygen and power, automatic isolation mechanisms, and adequate battery-powered emergency lighting to facilitate evacuation during power losses [
1,
2,
4]. Second, routine fire risk assessments and realistic, multidisciplinary OR fire drills should be implemented, including simulations involving patients under anesthesia with predefined team roles and hands-on training, as emphasized in international guidelines [
2,
4]. Finally, integrating a dedicated OR fire emergency protocol into hospital disaster plans is essential. This should include implementation of a clear “code red-OR algorithm,” structured communication pathways, and coordination with adjacent critical units to prevent escalation into a multidepartment disaster [
2,
4].
This incident illustrates how an unexpected electrical fire in a modern OR can rapidly escalate into a life-threatening emergency. Given the hazardous nature of contemporary surgical environments due to oxygen cylinders and numerous electrical equipment, preparedness must extend beyond commonly recognized fire scenarios to include environmental and electrical hazards. Proactive institutional planning, appropriate infrastructural safeguards, and realistic team-based training are necessary to ensure rapid, coordinated responses and to minimize harm when such rare but catastrophic events occur. As surgical environments become increasingly complex, reinforcing OR fire safety measures is more critical than ever.